Check the door manufacturer s instructions.
Acceptable gap under fire door.
In general clearance for those allowed gaps are as follows.
In general the gap should not exceed 3mm along the 2 long edges and across top of the door leaf to facilitate checking of the gap on site a bwf fire door alliance scheme gap tester is available on request here.
For general fire doors eg fd30 it s generally accepted that a threshold gap of up to 8mm is acceptable but i would contact the door manufacturer to to see what their recommended threshold gap is for that particular design of door.
Contains information on maximum gap allowances for different types of fire doors.
It should be noted that when a 762 2 6 door leaf which is hung on standard hinges swings open the diagonal measurement of the leaf becomes effective and will reduce the clearance on the lock side by between 1 and 1 5 mm depending on the width and thickness of the door leaf.
1 8 for more detailed gap information refer to nfpa 80 section 6 3 1 7 and section.
Nfpa 80 fire doors and other opening protectives.
For example the maximum door gap dimension for 3 4 hour and greater rated wood fire doors is 1 8 in no over tolerance dimension is permitted.
Under the bottom of a door.
The gap between the door leaf and the frame must be suitable for the intumescent seal fitted.
The gap at the bottom of the door is usually around 10mm for non smoke conditions but 3mm when smoke seals are required.
3 4 between door and frame.
When speaking with manufacturers however a common statement is that a fire doors gap of up to 8 mm underneath the door is permissible.
In general the gap should not exceed 3 mm.
This is probably just referring to normal fd30 applications as the fire door manufacturer is not involved in upgrading fire doors to cold seal protected standard fd30 s.